HEAT TRAPS

It is possible on installations where no heat trap is fitted

and the hot water outlet/plumbing rises from the water

heater connection at the top of the system, for the heated

water from the tank to circulate within the pipe.

During periods of no usage in the dwelling heated water rises

up the pipe until it cools and then falls back into the water

heater due to its increased density. This activity will increase

the heat loss from the system and increase running costs.

Most current Rheem models incorporate a dip tube which

conveys the hot water from the highest point inside the

concave top of the storage cylinder to the outlet connection

on the side of the cylinder. The dip tube acts as an integral

heat trap by restricting hot water in the cylinder from

circulating within the hot water plumbing.

AS3500.4 states that for installation using water heaters

with an integral heat trap (dip tube) a further heat trap is not

required.

The new Rheem range of electric stainless steel cylinders

with the hot water outlet at the top of the tank do require a

heat trap to be plumbed when taking the hot water line in an

upwards direction and across the dwelling to fixtures. The

trap needs to have a loop formed that extends 250mm lower

than the outlet at the top and then extends to the fixtures

being served (see diagram).

Jon Palfrey is Rheem Australia’s Training Manager. He

conducts training to plumbers and specifiers across the

southern states, covering the latest water heater technology

and key water heating issues facing plumbers.

RHEEM STELLAR

range of water filters

WaterMark Certified

Industry tested and proven to ensure

consistent trust and peace of mind.

I.M.P.A.C.T. 4-in-1

Aqua-Pure’s new filter technology is a

high capacity carbon block with a pleated

pharmaceutical quality 0.2 micron membrane.

‘Smart’ Indicator

Built in LED indicator that changes from

blue to red when it’s time to change filters.

Scan QR code for more information

or contact us on

1300 345 837

AVAILABLE FROM LEADING PLUMBING OUTLETS

HOT WATER OUTLET

IS LOCATED ON

TOP OF THE WATER

HEATER.

MINIMUM 250MM

FALL

TEMPERED WATER

OUTLET

COLD WATER

OUTLET

AN EXTERNAL HEAT

TRAP IS REQUIRED TO

BE INSTALLED

MUST BE WITHIN 1

METRE OF THE HOT

WATER OUTLET,

BEFORE THE

FIRST HOT WATER

BRANCH AND HAVE

A VERTICAL DROP

OF 250MM FROM

THE OUTLET OF THE

WATER HEATER

HOT OUTLET